    APPLICATION
    The Model DDP-105 is a general purpose proving switch designed for HVAC and Energy Management applications. The DDP-105 provides dual switching action: two separately-operated, independently-adjustable SPDT snap-acting switches are mounted on a common foot bracket. Differential pressures up to 2 inches w.c. can be measured. Because the two snap switches are set independently, an adjustable “deadband” can be established for control circuits
    requiring both high and low actuation points. Many control and alarm functions are possible: for instance, monitor two pressure sources and sense the ifferential for actuation at two independent set points.

    GENERAL DESCRIPTION & OPERATION
    Each of the two plated housings contains a diaphragm, a calibration spring and a snap-acting SPDT switch. There are two low pressure sample onnections (one for each switch assembly), and a common high pressure sample connection (located on the foot bracket between the two low pressure
    connections). All three sample connections accept ¼” OD metallic tubing via integral compression ferrule and nut fittings.

    MOUNTING
    Select a mounting location which is free from vibration. The DDP-105 must be mounted with the diaphragm in any vertical plane in order to obtain the lowest specified operating set point. Avoid mounting with the sample line connections in the “up” position. Surface mount via the two 3/16” diameter holes in the integral mounting bracket. The mounting holes are 7” apart.

    AIR SAMPLING CONNECTION
    The DDP-105 is designed to accept firm-wall sample lines of ¼” OD tubing by means of ferrule and nut compression connections. For sample lines of up to 10 feet, ¼” OD tubing is acceptable. For lines up to 20 feet, use ¼” ID tubing. For lines up to 60 feet, use ½” ID tubing. Adapters, suitable for slip-on flexible tubing are available: refer to Bulletin AFSFS 08.01. Locate the sampling probe a minimum of 1.5 duct diameters downstream from the air source. Install the sampling probe as close to the center of the airstream as possible. Refer to the dimensions drawing to identify the common high pressure inlet “H ” (on the foot bracket) and the two low pressure inlets “L” (on Element A and Element B). For each element, select one of the following options and connect the
    sample lines as recommended.

    POSITIVE PRESS URE ONLY: Connect the sample line to inlet H; inlet L remains open to the atmosphere.
    NEG ATIVE PRESS URE ONLY: Connect the sample line to inlet L; inlet H remains open to the atmosphere.
    TWO NEG ATIVE SAMPLES: Connect the higher negative sample to inlet L. Connect the lower negative sample to inlet H.
    TWO POSITIVE SAMPLES: Connect the higher positive sample to inlet H. Connect the lower positive sample to inlet L.
    ONE POSITIVE AND ONE NEGEG ATIVE SAMPLE: Connect the positive sample to inlet H. Connect the negative sample to inlet L.

    ELECTRICAL CONNECTIONS
    For each element, before pressure is applied to the diaphragm, the switch contacts will be in the normally closed (NC) position.The snap switch has 90º quick-connect terminals. For each element, wire alarm and control applications as shown in Figure 1.

    FIELD ADJUSTMENT
    The adjustment range of each of the 2 elements of the DDP 105 Air Switch is 0.05±.02” w.c. to 12.0” w.c.. To adjust an element’s set point, turn the adjusting screw counterclockwise until motion has stopped. Next, turn the adjusting screw 4 complete turns in a clockwise direction to engage the spring. From this point, the next ten turns will be used for the actual calibration. Each full turn represents approximately 1.2” w.c. Please note: To properly calibrate an air
    switch, a digital manometer or other measuring device should be used to confirm the actual set point.

    SPECIFICATIONS
    FOR MODEL DDP-105

    Operating temperature range:
    -40 to 176F (-40.0C to 80C).

    Approvals: UL, CSA.
    Shipping Weight: 1 lb. approx.

    Common Foot Bracket:
    Material: Cycolac® T4500.

    Sample Line Connector:
    Male,externally threaded, 7/16” – 24 UNS thread, complete with nut and self-aligning ferrule.

    Sample Line Connection:
    Connector will accept ¼” OD rigid or semi-rigid tubing (i.e., copper, aluminum or plastic). Tubing adaptors, suitable for slipping on flexible plastic tubing are available separately.

    SWITCHING ELEMENT “B”:
    Mounting position:
    Diaphragm vertical.

    Set Point Range:
    .05± .02” wc to 12.0”wc.

    Field adjustable “operate range”:
    .07” wc to 12.0” wc.

    Field adjustable “release range”:
    .04” wc to 11.2” wc.

    Approximate switching differential:
    Progressive; increasing from .02± .01” wc at minimum set point to approximately .1” wc at maximum set point.

    Measured media: Air.
    Life: 100,000 cycles minimum at ½ PSI maximum pressure each cycle and at maximum rated electrical load.

    Electrical rating:
    300 VA pilot duty at 115 to 277 VAC (60 Hz). 15a non-inductive to 277 VAC (60 Hz).

    Contact arrangement:
    SPDT.

    Position of switch contacts before pressure is applied:
    NC.

    Electrical Connections:
    90º quick-connect terminals.

    Sample Line Connector:
    Male,externally threaded, 7/16” – 24 UNS thread, complete with nut and self-aligning ferrule.

    Sample Line Connection:
    Connector will accept ¼” OD rigid or semi-rigid tubing (i.e., copper, aluminum or plastic). Tubing adaptors, suitable for slipping on flexible plastic tubing are available separately.

    SWITCHING ELEMENT “A”:
    Mounting position:
    Diaphragm vertical.

    Set Point Range:
    .05± .02” wc to 12.0”wc.

    Field adjustable “operate range”:
    .07” wc to 12.0” wc.

    Field adjustable “release range”:
    04” wc to 11.2” wc.

    Approximate switching differential:
    Progressive; increasing from .02± .01” wc at minimum set point to approximately .1” wc at maximum set point.

    Measured media:
    Air.

    Life:
    100,000 cycles minimum at ½ PSI maximum pressure each cycle and at maximum rated electrical load.

    Electrical rating:
    300 VA pilot duty at 115 to 277 VAC (60 Hz). 15a non-inductive to 277 VAC (60 Hz).

    Contact arrangement:
    SPDT.

    Position of switch contacts before pressure is applied:
    NC.

    Electrical Connections:
    90º quick-connect terminals.

    Sample Line Connector:
    Male,externally threaded, 7/16”– 24 UNS thread, complete with nut and self-aligning ferrule.

    Sample Line Connection:
    Connector wiill accept ¼” OD rigid or semi-rigid tubing (i.e., copper ,aluminum or plastic). Tubing adaptors, suitable for slipping on flexible plastic tubing are available sepa-rately.